
propagates over the cables then goes via the circuit breaker panel to start at the vari-
ous cables again. The wiring length can exceed 300m, which is considered as the
acceptable limit for a satisfactory useful throughput.
The electrical devices connected to the network are potential sources of electro-
magnetic disturbances for the PLC signal. Remember that the average length of the
electrical wiring between the switchboard and the farthest outlet should not exceed
200m.
Three-Phase Wiring
Buildings, large houses, professional premises, or plants have greater electrical
power requirements than a domestic dwelling; therefore, the electrical network is
often a three-phase network in them.
Four cables (neutral, phases 1, 2, and 3) start from the circuit breaker panel and
supply the outlets of the building. Figure 8.11 illustrates an example of three- phase
wiring in a building with several stories with the various electrical phases supplying
the building stories. Two cables starting from the switchboard travel all over each
story: a phase cable and the neutral cable.
The single cable that is common to the entire building is the neutral cable. The
other cables are electrically dissociated. It is important to remember that the PLC
signal flowing in one of the cables (neutral or phase cable) can be transmitted in the
other cables due to an induction phenomenon. This makes it possible to build the
topology of the PLC local area network by making optimal use of the properties of
the electrical wirings.
Topology of Electrical Networks 163
Figure 8.11 Topology of a three-phase electrical network for a large building
Kommentare zu diesen Handbüchern